مظلم خفيفة

GV5P150F Motor Circuit Breaker 3P, 150A, 36KA, Schneider

التوفر:

غير متوفر في المخزون


  • TeSys GV motor circuit breaker, 3 poles (3P), 150A/690V, for protection of 3-phase motors 55-75kW@400V.
  • It provides thermal magnetic protection and additional protections, breaking capacity Icu 36kA, start-stop control by rotary handle, connection for bars or cables with lugs (direct connection of cables with additional connectors).

قارن
  • TeSys GV motor circuit breaker, 3 poles (3P), 150A/690V, for protection of 3-phase motors 55-75kW@400V.
  • It provides thermal magnetic protection and additional protections, breaking capacity Icu 36kA, start-stop control by rotary handle, connection for bars or cables with lugs (direct connection of cables with additional connectors).
  • Thermal protection adjustable by dials with a setting current Ir in range 70-150A and a selectable tripping class 5, 10 or 20, magnetic protection at 15 In.
  • Additional protections with fixed pick-up include short time delay protection Isd at 13 Ir, phase unbalance and loss protection.
  • فهو يجعل المواقع الداخلية متاحة لكتل الاتصال الإضافية الإضافية (OF، SD)، ووحدات رحلة الجهد (MN، MX).
  • متعدد المعايير (IEC ، UL ، CSA ، CCC ، EAC ، Marine) ، متوافق مع Green Premium (RoHS / REACh).